Unique Name for the template.
Type: |
Alphanumeric |
Max Length: |
32 Characters |
Excluded: |
Unassigned |
Note: |
This name can be any alphanumeric that you choose, i.e., Refrigerators, Freezers, Incubators, etc. However, whatever system is used, each one must be unique. |
The Department that this template belongs to.
Configure: |
24 x 7 Alarm Time Matrix used to enable or disable alarming based on time of day and day of week.
Note: The Alarm Time Matrix can be enabled or disabled by checking or clearing the Alarm Time Enabled checkbox.
Configure: |
Alarm Enabled checkbox used to enable or disable all of the alarming functionality for this channel.
Checked: |
Alarming Enabled for this channel |
Cleared: |
Alarming Disabled for this channel |
Alarm Time Enabled checkbox used to enable or disable all of the Alarm Time Matrix functionality for this channel.
Checked: |
Alarm Time Matrix Enabled for this channel |
Cleared: |
Alarm Time Matrix Disabled for this channel |
The Low Alarm Set Point of this channel.
Note: Functions in conjunction with the Low Alarm Delay time of this channel.
Type: |
Numeric |
Range: |
-1000 to 1000 |
Format: |
####.## |
The Low Alarm Delay time (minutes) of this channel sets how long the value of the channel must be equal to or less than the Low Alarm Set Point of this channel in order for a Low Alarm to be triggered.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The Low Alarm Reset time (minutes) of this channel sets how long the value of the channel must be greater than the Low Alarm Set Point of this channel in order for a Low Alarm to recover.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The Low Warn Set Point of this channel.
Note: Functions in conjunction with the Low Warn Delay time of this channel.
Type: |
Numeric |
Range: |
-1000 to 1000 |
Format: |
####.## |
The Low Warn Delay time (minutes) of this channel sets how long the value of the channel must be equal to or less than the Low Warn Set Point of this channel in order for a Low Warning to be triggered.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The Low Warn Reset time (minutes) of this channel sets how long the value of the channel must be greater than the Low Warn Set Point of this channel in order for a Low Warning to recover.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The Low Force Alarm Set Point of this channel. If this set point is reached then the Low Alarm Delay time of this channel will be bypassed and a Low Force Alarm will be immediately triggered.
Type: |
Numeric |
Range: |
-1000 to 1000 |
Format: |
####.## |
The Low Rewarn Value of this channel sets how much further below the Low Alarm Set Point of this channel the value must reach in order for a Low Rewarn to be triggered. Used to prevent runaway conditions.
Type: |
Numeric |
Range: |
0 to 100 |
Format: |
###.# |
Note: |
Enter Zero (0) to Disable |
The Low Alarm Echo time (minutes) of this channel sets how long the value of the channel must be equal to or less than the Low Alarm Set Point of this channel after a Low Alarm has sounded in order for a Low Alarm Echo to be triggered. Used as a reminder that the channel is still in a Low Alarm state.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
#### |
Note: |
Enter Zero (0) to Disable |
The High Alarm Set Point of this channel.
Note: Functions in conjunction with the High Alarm Delay time of this channel.
Type: |
Numeric |
Range: |
-1000 to 1000 |
Format: |
####.## |
The High Alarm Delay time (minutes) of this channel sets how long the value of the channel must be equal to or greater than the High Alarm Set Point of this channel in order for a High Alarm to be triggered.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The High Alarm Reset time (minutes) of this channel sets how long the value of the channel must be less than the High Alarm Set Point of this channel in order for a High Alarm to recover.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The High Warn Set Point of this channel.
Note: Functions in conjunction with the High Warn Delay time of this channel.
Type: |
Numeric |
Range: |
-1000 to 1000 |
Format: |
####.## |
The High Warn Delay time (minutes) of this channel sets how long the value of the channel must be equal to or greater than the High Warn Set Point of this channel in order for a High Warning to be triggered.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The High Warn Reset time (minutes) of this channel sets how long the value of the channel must be less than the High Warn Set Point of this channel in order for a High Warning to recover.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
####.# |
The High Force Alarm Set Point of this channel. If this set point is reached then the High Alarm Delay time of this channel will be bypassed and a High Force Alarm will be immediately triggered.
Type: |
Numeric |
Range: |
-1000 to 1000 |
Format: |
####.## |
The High Rewarn Value of this channel sets how much further above the High Alarm Set Point of this channel the value must reach in order for a High Rewarn to be triggered. Used to prevent runaway conditions.
Type: |
Numeric |
Range: |
0 to 100 |
Format: |
###.# |
Note: |
Enter Zero (0) to Disable |
The High Alarm Echo time (minutes) of this channel sets how long the value of the channel must be equal to or greater than the High Alarm Set Point of this channel after a High Alarm has sounded in order for a High Alarm Echo to be triggered. Used as a reminder that the channel is still in a High Alarm state.
Type: |
Numeric |
Range: |
0 to 1440 |
Format: |
#### |
Note: |
Enter Zero (0) to Disable |
Previous |
Selects the Previous Alarm Settings Template by Number (Number Not Shown) |
Edit |
Places the form into Update mode for Updating the Alarm Settings Template |
New |
Places the form into Insert mode for Adding a new Alarm Settings Template |
Displays a Printable Report for the selected Alarm Settings Template |
|
Print All |
Displays a Printable Report for all of the Alarm Settings Templates |
Print Channel List |
Displays a Printable Report listing all Channels that have this Alarm Settings Template assigned to them |
Insert |
Insert Mode - Validates the page and Adds the Alarm Settings Template if there are no errors |
Update |
Update Mode - Validates the page and Updates the Alarm Settings Template if there are no errors |
Cancel |
Update / Insert Mode - Cancels the Update or Insert and places the page in View mode |
Next |